Balanced draft boilers are generally used negative furnace pressure. When both forced draft and induced draft are used together, at some point in the system the pressure will be same as that of atmosphere. Therefore the furnace pressure must be negative to prevent hot gas leakage. Excessive vacuum in the furnace however produces heat losses through air infiltration. The most desirable condition is that the one have a very slight negative pressure of the top of furnace.
■ TRIP : The term trip refers to an action that is initiated by the control system and which forces a device or devices to a pre-determined state. Example of Trip Signals: Close Valve, Open Valve, Stop motor, etc. The Safety Instrument System (SIS) or a Hardwired systems normally initiate trips, however the PLCs or DCS may also initiate trips provided the necessary independence and SIL ratings are met.Once a device or devices have been forced to a pre-determined state by the action of a Trip they will remain in that state until the Trip is manually reset by a conscious operator action. For example: High level in a vessel initiates a trip system which stops the pump feeding that vessel, the pump will remain stopped even if the level in the vessel falls to a safe level. The Trip must be ‘reset’ by the operator before the pump can be re-started. The Trip can only be ‘reset’ if the level in the tank has fallen to a safe level. Resetting the Trip will no...