Explain tuning of controllers.

Tuning basically involves adjustment of proportional. Integral  and derivative parameters to achieve good control. The gain, time constants, and dead times around the loop will dictate the settings of various parameters of the controller.

Tuning methods are broadly classified into two :
1. Closed Loop Method : e.g. Ultimate Gain Method.
2. Open Loop Method : e.g. process Reaction curve.


Ultimate gain method:
The term ultimate gain was attached to this method because its use require the determination of the ultimate gain (sensitivity) and ultimate period. The ultimate sensitivity Ku is the maximum allowable value of gain (for a controller with only Proportional mode) for which the system is stable. The ultimate period is the period of the response with the gain set at its ultimate value.

Process reaction curve :
To deter mine the process reaction curve, the following steps are recommended. :
1. Let the system come to steady state at the normal load level.
2. Place the controller on manual.
3. Manually set the output of the controller at the value at which it was operating in the automatic mode.
4. Allow the system to reach the steady state.
5. With controller on manual, impose a step changes in the output of controller, which is an signal to value.
6. Record the response of controlled variable.
7. Return the controller output to its previous value and return the controller to auto operation.

Comments

Popular posts from this blog

BASICS OF TRIPS, INTERLOCKS, PERMISSIVES & SEQUENCES

■ TRIP : The term trip refers to an action that is initiated by the control system and which forces a device or devices to a pre-determined state. Example of Trip Signals: Close Valve, Open Valve, Stop motor, etc. The Safety Instrument System (SIS) or a Hardwired systems normally initiate trips, however the PLCs or DCS may also initiate trips provided the necessary independence and SIL ratings are met.Once a device or devices have been forced to a pre-determined state by the action of a Trip they will remain in that state until the Trip is manually reset by a conscious operator action. For example: High level in a vessel initiates a trip system which stops the pump feeding that vessel, the pump will remain stopped even if the level in the vessel falls to a safe level. The Trip must be ‘reset’ by the operator before the pump can be re-started. The Trip can only be ‘reset’ if the level in the tank has fallen to a safe level. Resetting the Trip will no...

Instrument Range Selection

Instrument range shall be selected based on operating range of process to be measured. In common practice, it is recommended to select instrument with full scale range that can give operating process reading between 30% and 70% especially for pressure gauge. The following is an example of selecting pressure gauge range Given Process data: Minimum operating pressure: 5 barg Maximum operating pressure: 9.5 barg Maximum Design pressure: 25 barg Available standard Pressure Gauge range: 0 – 10 barg, 0 – 16 barg, 0 – 25 barg [X] Selecting 0-10 barg will give 95% reading during maximum operating condition. Instrument has only narrow margin above maximum operating pressure. [√] Selecting 0-16 barg range will give best reading during operating condition. However, the maximum overpressure of pressure gauge is commonly 1.3x of the maximum scale which is only 16×1.3 = 20.8 barg. In such case, pressure gauge shall be equipped with overrange protector to withstand ...

What is Foundation Fieldbus?

Foundation Fieldbus is an all-digital, serial, two-way communications system that serves as a Local Area Network (LAN) for factory/plant instrumentation and control devices. The Fieldbus environment is the base level group of the digital networks in the hierarchy of plant networks. Foundation Fieldbus is used in both process and manufacturing automation applications and has a built-in capability to distribute the control application across the network. Unlike proprietary network protocols, Foundation Fieldbus is neither owned by any individual company, nor regulated by a single nation or standards body. The Foundation Fieldbus, a not-for-profit organization consisting of more than 100 of the world's leading controls and instrumentation suppliers and end users, controls the technology. While Foundation Fieldbus retains many of the desirable features of the 4-20 mA analogue system, such as a standardized physical interface to the wire, bus-powered devices on a single wire, and intr...